How does an excess flow valve for LPG systems work?

5. February 2018/in LPG Everyday, LPG in Commerce, LPG in Private Housholds

Inhaltsverzeichnis

  • Design and installation
  • Background and purpose of this component
  • A simple explanation of the function:
  • Can an excess flow valve be used several times?
  • What should be taken into account in terms of design?
Approximate reading time: 4 minutes

The German LPG Association (DVFG) obliges the operator of an LPG system for private purposes in accordance with the technical rules for LPG (for short: TRF 2012) to incorporate an excess flow valve. Each new gas heating system must therefore have this safety component. If you make major changes to your LPG heating system, you must install an excess flow valve.

This blog post provides information on how to operate an excess flow valve (GS) and how it protects residents from dangerous gas leakage.

Design and installation

An excess flow valve is a safety component in the LPG system. There is a type of valve inside this component. This consists of a valve seat, a spring and a valve plate. Internal damping ensures fault-free operation of the LPG system when the output is changed.

Background and purpose of this component

A gas line must never be put into operation without prior inspection by the specialist. First, ensure that all pipes and fittings are in perfect condition. In addition, it must be checked whether there is any damage on the pipe or any leakage. The gas is only then inserted into the line.

YouTube

By loading the video you accept YouTube’s privacy policy.
Learn more

Load video

Despite intensive inspection, the gas line is not generally protected from leaks or manipulation in the long term.In the event of such defects, the excess flow valve will kick in and stop the LPG supply. The GS is a component that ensures manipulation security. It responds if the set flow rate is exceeded, for example by loosened compression fittings or disconnected piping, and it blocks the gas flow. As an overflow opening is required for the automatic opening, the gas shut-off valve must be closed as quickly as possible after the safety device responds.

A simple explanation of the function:

An excess flow valve responds to the LPG flowing through it. If, as described above, there is a defect in the LPG system or the gas line itself, the gas will flow through the GS more quickly. This results in a pressure drop in the gas line behind the excess flow valve. At the same time, gas flows into the supply line so that there are different pressures in the lines upstream and downstream of the installed excess flow valve. This uneven pressure ratio means that the valve plate sits in the valve seat of the valve. This process blocks the gas supply into the downstream piping.

The following example features a typical tank system with an LPG tank.The excess flow valve is installed after the second stage of the pressure control.

The example shows a typical tank system with an LPG tank. The excess flow valve is installed after the second stage of the pressure control.

Can an excess flow valve be used several times?

If the gas line is checked and tight again, gas flows from the supply line through the overflow opening of the excess flow valve into the gas line. This process means that gas pressure builds up in the lines downstream of the excess flow valve. If the pressure is equalised, the GS opens and is ready for use. Therefore, an excess flow valve can be used several times.

Caution:When restarting a gas line or a gas system, it is to be ensured that the gas is slowly let into the line as otherwise the excess flow valve closes the inside valve and the gas supply stops. In this case, the following lines are only filled through the overflow opening and this can take a longer period depending on the line length.

If the LPG cylinder system is set up according to the TRF and it uses 33-kilogram cylinders, the operator requires an excess flow valve. This is located between the pressure regulator and the supply line.

If the LPG cylinder system is set up according to the TRF and it uses 33-kilogram cylinders, the operator requires an excess flow valve.This is located between the pressure regulator and the supply line.

What should be taken into account in terms of design?

The following parameters must be taken into account when dimensioning your excess flow valve:

  • The supply pressure. Because, depending on the pressure ratio, the site of installation of the excess flow valve changes.
  • The sum of all connected loads
  • The nominal values of the gas line

The heating fitter or your LPG supplier will be happy to help you select the right excess flow valve based on the appropriate values.

Here you can also find interesting information on what to consider when purchasing a gas heater.

Please observe our note that the work on the system described above may only be carried out by a qualified person.

Share this entry
  • Share on Facebook
  • Share on Twitter
  • Share on WhatsApp
  • Share on LinkedIn
  • Share on Reddit
  • Share by Mail
https://www.gok-blog.de//wp-content/uploads/2020/10/GOK-BLOG-Logo.svg 0 0 GOK Media https://www.gok-blog.de//wp-content/uploads/2020/10/GOK-BLOG-Logo.svg GOK Media2018-02-05 07:00:222018-02-05 07:00:22How does an excess flow valve for LPG systems work?
You might also like
How does an over-pressure safety device S2SR work?
When do I need a diaphragm-controlled anti-siphon device?
How can I check the functionality of the limit indicator?
How does a limit indicator work?
Is it mandatory to have a gas anti-tilt device for outdoor heaters, patio heaters and radiant heaters?
Can I heat my motorhome and caravan while driving?
  • Search

  • Filter

  • Category

  • Reset all filters
Approximate reading time: 8 minutes

Information regarding technical systems

This blog will never ask members of the public or unqualified persons to make changes to or fiddle around with technical systems themselves.

In accordance with the Industrial Safety Regulation (BetrSichV), a qualified person must take care of a system which requires monitoring.

A qualified person is someone who has the specific specialist knowledge required. This knowledge is gained by way of a professional apprenticeship, corresponding professional experience or current occupational activity.

Please note that the texts are based on information, regulations and standards for Germany. Please always check the rules and regulations in the relevant country of destination and consult specialists if necessary.

Regler- und Armaturen-Gesellschaft mbH & Co. KG

Address

Obernbreiter Straße 2-18
97340 Marktbreit / Germany

Phone: +49 9332 404-0
Fax: +49 9332 404-49

Email: info@gok.de
Website: www.gok.de

Quick selection

  • LPG Leisure Time
  • LPG Everyday
  • Liquid Media & Tank Management
  • General
  • About GOK
  • Product sales
  • Legal notice
  • Image sources
  • Privacy policy
  • Cookie settings
Scroll to top